% Device definition for Climatrix, Digital inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixDigital NAMED "Climatrix Dig.1" TYPEID 21380 IS

  PARAMETER
    Id    : "Adress";

  PUBLIC

    D1    : "DangerAlarm(A)" ;
    D2    : "CriticAlarm(A)" ;
    D3    : "LowAlarm(B)"    ;
    D4    : "WarningAlarm(C)";
    D5    : "ManualMode"     ;
    D6    : "ComTestPuls"    ;

    D11   : "EmergencyStop"  ;
    D12   : "Ext.Input1"     ;
    D13   : "Ext.Input2"     ;
    D14   : "Summer/Winter"  ;
    D15   : "Aux.Input"      ;

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalInput NAMED "Läs Status 1-19" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(0);      % Start adress (1-1)
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8                % ((Number of inputs / 8) + (Rest>0)) + 5
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
     %DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(
                       IF (DATA & 1)   THEN D1 := 1; ELSE D1 := 0; ENDIF;
                       IF (DATA & 2)   THEN D2 := 1; ELSE D2 := 0; ENDIF;
                       IF (DATA & 4)   THEN D3 := 1; ELSE D3 := 0; ENDIF;
                       IF (DATA & 8)   THEN D4 := 1; ELSE D4 := 0; ENDIF;
                       IF (DATA & 16)  THEN D5 := 1; ELSE D5 := 0; ENDIF;
                       IF (DATA & 32)  THEN D6 := 1; ELSE D6 := 0; ENDIF;
     %                 IF (DATA & 64)  THEN D7 := 1; ELSE D7 := 0; ENDIF;
     %                 IF (DATA & 128) THEN D8 := 1; ELSE D8 := 0; ENDIF;
                       );
      DATA[4]  -> BYTE(
     %                 IF (DATA & 1)   THEN D9 := 1; ELSE D9 := 0; ENDIF;
     %                 IF (DATA & 2)   THEN D10:= 1; ELSE D10:= 0; ENDIF;
                       IF (DATA & 4)   THEN D11:= 1; ELSE D11:= 0; ENDIF;
                       IF (DATA & 8)   THEN D12:= 1; ELSE D12:= 0; ENDIF;
                       IF (DATA & 16)  THEN D13:= 1; ELSE D13:= 0; ENDIF;
                       IF (DATA & 32)  THEN D14:= 1; ELSE D14:= 0; ENDIF;
                       IF (DATA & 64)  THEN D15:= 1; ELSE D15:= 0; ENDIF;
     %                 IF (DATA & 128) THEN D16:= 1; ELSE D16:= 0; ENDIF;
                       );
     %DATA[5]  -> BYTE(
     %                 IF (DATA & 1)   THEN D17:= 1; ELSE D17:= 0; ENDIF;
     %                 IF (DATA & 2)   THEN D18:= 1; ELSE D18:= 0; ENDIF;
     %                 IF (DATA & 4)   THEN D19:= 1; ELSE D19:= 0; ENDIF;
     %                 IF (DATA & 8)   THEN D20:= 1; ELSE D20:= 0; ENDIF;
     %                 );

    TIMEOUT 1000

  END;

END;


%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix, Indikation/Alarm inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 initial version
%
DEVICETYPE ClimatrixAlarm NAMED "Climatrix Dig.2" TYPEID 21381 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC
    AL20 : "OutAirDamper"    ;
    AL21 : "ExtracAirDamper" ;
    AL22 : "FireDamperClose" ;
    AL23 : "FireDamperOpen"  ;
    AL24 : "FireDamperNoMov" ;
   %AL25 : ""                ;
    AL26 : "FanAlarm"        ;
    AL27 : "SupplyFanAlarm"  ;
    AL28 : "SupplyFanFeedb." ;
    AL29 : "SupplyFanDevia." ;
    AL30 : "ExhaustFanAlarm" ;
    AL31 : "ExhaustFanFeedb" ;
    AL32 : "ExhaustFanDevia" ;
    AL33 : "FanOperat.Hours" ;
   %AL34 : ""                ;
   %AL35 : ""                ;
    AL36 : "CoolDXAlarm"     ;
    AL37 : "CoolDXFeedb."    ;
    AL38 : "CoolPumpAlarm"   ;
    AL39 : "CoolPumpFeedb."  ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalAlarm NAMED "Läs Larm 20-39" IS

    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(19);     % Start adress (20-1)
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8                % ((Number of inputs / 8) + (Rest>0)) + 5
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
     %DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(
                       IF (DATA & 1)   THEN AL20:= 1; ELSE AL20:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL21:= 1; ELSE AL21:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL22:= 1; ELSE AL22:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL23:= 1; ELSE AL23:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL24:= 1; ELSE AL24:= 0; ENDIF;
    %                  IF (DATA & 32)  THEN AL25:= 1; ELSE AL25:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL26:= 1; ELSE AL26:= 0; ENDIF;
                       IF (DATA & 128) THEN AL27:= 1; ELSE AL27:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(
                       IF (DATA & 1)   THEN AL28:= 1; ELSE AL28:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL29:= 1; ELSE AL29:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL30:= 1; ELSE AL30:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL31:= 1; ELSE AL31:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL32:= 1; ELSE AL32:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL33:= 1; ELSE AL33:= 0; ENDIF;
    %                  IF (DATA & 64)  THEN AL34:= 1; ELSE AL34:= 0; ENDIF;
    %                  IF (DATA & 128) THEN AL35:= 1; ELSE AL35:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(
                       IF (DATA & 1)   THEN AL36:= 1; ELSE AL36:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL37:= 1; ELSE AL37:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL38:= 1; ELSE AL38:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL39:= 1; ELSE AL39:= 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix, Indikation/Alarm inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 initial version
%
DEVICETYPE ClimatrixAlarm NAMED "Climatrix Dig.3" TYPEID 21382 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    AL40 : "HeatRecAlarm"    ;
    AL41 : "HeatRecPumpAlar" ;
    AL42 : "HeatRecPumpFeed" ;
    AL43 : "HeatRecFrostMon" ;
    AL44 : "HeatRecEffAlarm" ;
    AL45 : "HeatPumpAlarm"   ;
    AL46 : "HeatPumpFeedb."  ;
    AL47 : "HeatFrostMonito" ;
    AL48 : "Elec.HeatAlarm"  ;
    AL49 : "Cool2DXAlarm"    ;
    AL50 : "Cool2DXFeedb."   ;
    AL51 : "Cool2PumpAlarm"  ;
    AL52 : "Cool2PumpFeedb." ;
    AL53 : "Heat2PumpAlarm"  ;
    AL54 : "Heat2PumpFeedb." ;
    AL55 : "Heat2FrostMon."  ;
    AL56 : "Elec.Heat2Alarm" ;
    AL57 : "SupplyTempDev."  ;
    AL58 : "RoomTempDev."    ;
   %AL59 : ""                ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalAlarm NAMED "Läs larm 40-59" IS

    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(39);     % Start adress (40-1)
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8                % ((Number of inputs / 8) + (Rest>0)) + 5
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
     %DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(
                       IF (DATA & 1)   THEN AL40:= 1; ELSE AL40:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL41:= 1; ELSE AL41:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL42:= 1; ELSE AL42:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL43:= 1; ELSE AL43:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL44:= 1; ELSE AL44:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL45:= 1; ELSE AL45:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL46:= 1; ELSE AL46:= 0; ENDIF;
                       IF (DATA & 128) THEN AL47:= 1; ELSE AL47:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(
                       IF (DATA & 1)   THEN AL48:= 1; ELSE AL48:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL49:= 1; ELSE AL49:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL50:= 1; ELSE AL50:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL51:= 1; ELSE AL51:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL52:= 1; ELSE AL52:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL53:= 1; ELSE AL53:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL54:= 1; ELSE AL54:= 0; ENDIF;
                       IF (DATA & 128) THEN AL55:= 1; ELSE AL55:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(
                       IF (DATA & 1)   THEN AL56:= 1; ELSE AL56:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL57:= 1; ELSE AL57:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL58:= 1; ELSE AL58:= 0; ENDIF;
     %                 IF (DATA & 8)   THEN AL59:= 1; ELSE AL59:= 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix, Indikation/Alarm inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 initial version
%
DEVICETYPE ClimatrixAlarm NAMED "Climatrix Dig.4" TYPEID 21383 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

   %AL60 : ""                ;
   %AL61 : ""                ;
    AL62 : "HumidityFeedb."  ;
    AL63 : "Humid.PumpAlarm" ;
    AL64 : "Humid.PumpFeedb" ;
    AL65 : "SupplyHumid.Dev" ;
    AL66 : "RoomHumidDev"    ;
    AL67 : "DewPoint"        ;
   %AL68 : "                 ;
   %AL69 : "                 ;
    AL70 : "FilterAlarm"     ;
    AL71 : "SupplyFiltAlarm" ;
    AL72 : "ExhaustFilAlarm" ;
    AL73 : "FireAlarm"       ;
    AL74 : "SuppTempFireAla" ;
    AL75 : "ExhaTempFireAla" ;
    AL76 : "AuxiliaryAlarm"  ;
    AL77 : "ManualMode"      ;
    AL78 : "ModbusComAlarm"  ;
   %AL79 : "                 ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalAlarm NAMED "Läs larm 60-79" IS

    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(59);     % Start adress (50-1)
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8                % ((Number of inputs / 8) + (Rest>0)) + 5
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
     %DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(
     %                 IF (DATA & 1)   THEN AL60:= 1; ELSE AL60:= 0; ENDIF;
     %                 IF (DATA & 2)   THEN AL61:= 1; ELSE AL61:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL62:= 1; ELSE AL62:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL63:= 1; ELSE AL63:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL64:= 1; ELSE AL64:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL65:= 1; ELSE AL65:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL66:= 1; ELSE AL66:= 0; ENDIF;
                       IF (DATA & 128) THEN AL67:= 1; ELSE AL67:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(
     %                 IF (DATA & 1)   THEN AL68:= 1; ELSE AL68:= 0; ENDIF;
     %                 IF (DATA & 2)   THEN AL69:= 1; ELSE AL69:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL70:= 1; ELSE AL70:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL71:= 1; ELSE AL71:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL72:= 1; ELSE AL72:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL73:= 1; ELSE AL73:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL74:= 1; ELSE AL74:= 0; ENDIF;
                       IF (DATA & 128) THEN AL75:= 1; ELSE AL75:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(
                       IF (DATA & 1)   THEN AL76:= 1; ELSE AL76:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL77:= 1; ELSE AL77:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL78:= 1; ELSE AL78:= 0; ENDIF;
     %                 IF (DATA & 8)   THEN AL79:= 1; ELSE AL79:= 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix, Indikation/Alarm inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 initial version
%
DEVICETYPE ClimatrixAlarm NAMED "Climatrix Dig.5" TYPEID 21384 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    AL80 : "OutAirTemp"      ;
    AL81 : "SupplyAirTemp"   ;
    AL82 : "HeatFrostTemp"   ;
    AL83 : "RoomTemp"        ;
    AL84 : "RoomTemp2"       ;
    AL85 : "ExhaustAirTemp"  ;
    AL86 : "ExtractAirTemp"  ;
    AL87 : "HeatRecSuppTemp" ;
    AL88 : "HeatRecWateTemp" ;
    AL89 : "SupplyAirTemp2"  ;
    AL90 : "Heat2FrostTemp"  ;
    AL91 : "AuxiliaryTemp"   ;
    AL92 : "OutAirHumidiRel" ;
    AL93 : "SupAirHumidiRel" ;
    AL94 : "RoomHumidiRelat" ;
    AL95 : "SupplyAirFlow"   ;
    AL96 : "ExhaustAirFlow"  ;
    AL97 : "SupplyAirPress"  ;
    AL98 : "ExhaustAirPress" ;
    AL99 : "HeatRFrostPress" ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalAlarm NAMED "Läs larm 80-99" IS

    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(79);     % Start adress (80-1)
      DATA[4]  := RWORD(20);     % Number of inputs

    ANSWER SIZE 8                % ((Number of inputs / 8) + (Rest>0)) + 5
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
     %DATA[2]   = BYTE(3);
      DATA[3]  -> BYTE(
                       IF (DATA & 1)   THEN AL80:= 1; ELSE AL80:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL81:= 1; ELSE AL81:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL82:= 1; ELSE AL82:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL83:= 1; ELSE AL83:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL84:= 1; ELSE AL84:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL85:= 1; ELSE AL85:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL86:= 1; ELSE AL86:= 0; ENDIF;
                       IF (DATA & 128) THEN AL87:= 1; ELSE AL87:= 0; ENDIF;
                       );
      DATA[4]  -> BYTE(
                       IF (DATA & 1)   THEN AL88:= 1; ELSE AL88:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL89:= 1; ELSE AL89:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL90:= 1; ELSE AL90:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL91:= 1; ELSE AL91:= 0; ENDIF;
                       IF (DATA & 16)  THEN AL92:= 1; ELSE AL92:= 0; ENDIF;
                       IF (DATA & 32)  THEN AL93:= 1; ELSE AL93:= 0; ENDIF;
                       IF (DATA & 64)  THEN AL94:= 1; ELSE AL94:= 0; ENDIF;
                       IF (DATA & 128) THEN AL95:= 1; ELSE AL95:= 0; ENDIF;
                       );
      DATA[5]  -> BYTE(
                       IF (DATA & 1)   THEN AL96:= 1; ELSE AL96:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL97:= 1; ELSE AL97:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL98:= 1; ELSE AL98:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL99:= 1; ELSE AL99:= 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix, Indikation/Alarm inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 initial version
%
DEVICETYPE ClimatrixAlarm NAMED "Climatrix Dig.6" TYPEID 21385 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    AL100 : "OutAirDamper"    ;   % 1x0100 Air quality
    AL101 : "ExtracAirDamper" ;   % 1x0101 External setpoint
    AL102 : "FireDamperClose" ;   % 1x0102 Roomunit 1
    AL103 : "FireDamperOpen"  ;   % 1x0103 Roomunit 2

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM DigitalAlarm NAMED "Läs larm 100-103" IS

    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(02);       % Modbus command "02h" read discrete input (bit)
      DATA[2]  := RWORD(99);     % Start adress (100-1)
      DATA[4]  := RWORD(4);      % Number of inputs

    ANSWER SIZE 6                % ((Number of inputs / 8) + (Rest>0)) + 5
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(02);
     %DATA[2]   = BYTE(1);
      DATA[3]  -> BYTE(
                       IF (DATA & 1)   THEN AL100:= 1; ELSE AL100:= 0; ENDIF;
                       IF (DATA & 2)   THEN AL101:= 1; ELSE AL101:= 0; ENDIF;
                       IF (DATA & 4)   THEN AL102:= 1; ELSE AL102:= 0; ENDIF;
                       IF (DATA & 8)   THEN AL103:= 1; ELSE AL103:= 0; ENDIF;
                       );

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Digital outputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Kvittera genom att öka kanalvärdet kopplat till "Kvittering".
% Om man har en checkbox (kryssruta) för att utföra kvittering går det kanske
% att koppla en logisk funktion som efter viss timeout ställer tillbaka
% kvitteringskanalen (och checkboxen). Den timeouten måste anpassas efter
% skriptets ställda uppdateringstid.
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixDigitalOut NAMED "Climatrix SetDU" TYPEID 21386 IS

  PARAMETER
    Id   : "Adress";

    Ack  : "Acknowledge"    ;   % 0x01 Alarm acknowledge              Off*On

   %DU2  : "EnableComTest"  ;   % 0x02 Enable communicationtest       No*Yes
   %DU3  : "ComTestPuls"    ;   % 0x03 Communicationtest puls         0*1
   %DU4  : "FireDamperTest" ;   % 0x04 Fire damper test               Passive*Active
   %DU7  : "EnergyMeterRes.";   % 0x07 Energymeeter reset partial     Passive*ActiveTVal
   %DU11 : "EmergencyStop"  ;   % 0x11 Emergency stop input           Off*On, (I/O)
   %DU12 : "ExternalIn1"    ;   % 0x12 External control input 1       Off*On, (I/O)
   %DU13 : "ExternalIn2"    ;   % 0x13 External control input 2       Off*On, (I/O)
   %DU14 : "Summer/Winter"  ;   % 0x14 Summer/Winter changeover input Winter*Summer,I/O
   %DU15 : "FireAlarm"      ;   % 0x15 Fire alarm input               OK*Alarm,I/O

  PUBLIC

  PRIVATE
    Started;
    AckMemory;
    Cnt;

  BAUDRATE 9600;
  CHECKSUM MODBUS SWAPPED;

  TELEGRAM WriteDISET1 NAMED "Sätt Dig.Status" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(05);       % Modbus command "05h" Set coil status (bit)
      DATA[2]  <- RWORD(         %
        Cnt := Cnt + 1;
        IF Cnt>8 THEN Cnt:=0; ENDIF;
        DATA := 6;                   % Digital reg 7
       %IF    Cnt=0 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=1 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=2 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=3 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=4 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=5 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=6 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=7 THEN DATA := 6;  % Digital reg 7
       %ELSIF Cnt=8 THEN DATA := 6;  % Digital reg 7
       %ENDIF;
      );
      DATA[4]  <- RWORD(
        IF Ack THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %IF    Cnt=0 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=1 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=2 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=3 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=4 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=5 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=6 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=7 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ELSIF Cnt=8 THEN IF DO14 THEN DATA:=65280; ELSE DATA:=0; ENDIF;
       %ENDIF;
      );

    ANSWER SIZE 8
      DATA[0]   = BYTE(Id);
      DATA[1]   = HEX(05);

    TIMEOUT 1000
  END;

  TELEGRAM Acknowledge NAMED "Larmkvittering" IS

    QUESTION
      DATA[0]  := BYTE(Id);
      DATA[1]  := HEX(05);                 %Write singel coil
      DATA[2]  <- RWORD(DATA := 0;);       %Start adress (regnr-1)
      DATA[4]  <- RWORD(IF (Started = 0) THEN
                          AckMemory := Ack;
                          Started   := 1;
                        ENDIF;
                        IF (Ack > AckMemory) THEN
                          DATA := 65280;   % FF00h
                        ELSE
                          DATA := 0;
                        ENDIF;
                        AckMemory := Ack;
                        );

    ANSWER SIZE 8
      DATA[0] = BYTE(Id);
      DATA[1] = HEX(05);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA1 NAMED "Climatrix Reg.1" TYPEID 21387 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "Act.OperatMode"       ;

    V2  : "Act.FanStep"          ;
    V3  : "Man.OperatStep"       ;
    V4  : "Man.OperatSt/Te"      ;
    V5  : "Act.TimePrStep"       ;
    V6  : "Act.TimePrSt/Te"      ;
    V7  : "Act.OpmodeExtCt"      ;
    V8  : "FireDamperState"      ;
    V9  : "OutAirDamperCom"      ;
    V10 : "ExtAirDamperCom"      ;
    V11 : "FireDamperCom"        ;
    V12 : "SupplyFanCom"         ;
    V13 : "SupplyFanSignal" ["%"];
    V14 : "ExhaustFanCom"        ;
    V15 : "ExhaustFanSigna" ["%"];
   %V16 : "
    V17 : "CoolOutSignal"   ["%"];
    V18 : "CoolPumpCom"          ;
    V19 : "CoolDXCom"            ;
    V20 : "HeatRec.Signal"  ["%"];

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg. 17-36" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(16);     % Start address register (17-1)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(V1 := DATA;);
      DATA[5]  -> RWORD(V2 := DATA;);
      DATA[7]  -> RWORD(V3 := DATA;);
      DATA[9]  -> RWORD(V4 := DATA;);
      DATA[11] -> RWORD(V5 := DATA;);
      DATA[13] -> RWORD(V6 := DATA;);
      DATA[15] -> RWORD(V7 := DATA;);
      DATA[17] -> RWORD(V8 := DATA;);
      DATA[19] -> RWORD(V9 := DATA;);
      DATA[21] -> RWORD(V10:= DATA;);
      DATA[23] -> RWORD(V11:= DATA;);
      DATA[25] -> RWORD(V12:= DATA;);
      DATA[27] -> RWORD(V13:= DATA;);
      DATA[29] -> RWORD(V14:= DATA;);
      DATA[31] -> RWORD(V15:= DATA;);
     %DATA[33] -> RWORD(V16:= DATA;);
      DATA[35] -> RWORD(V17:= DATA;);
      DATA[37] -> RWORD(V18:= DATA;);
      DATA[39] -> RWORD(V19:= DATA;);
      DATA[41] -> RWORD(V20:= DATA;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA2 NAMED "Climatrix Reg.2" TYPEID 21388 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "HeatRec.PumpCom"      ;
    V2  : "HeatDamperSigna" ["%"];
    V3  : "HeatDamperValue" ["%"];
    V4  : "HeatSignal"      ["%"];
    V5  : "HeatPumpCom."         ;
    V6  : "El.HeatSignal"   ["%"];
    V7  : "El.HeatCom."          ;
    V8  : "Cool2Signal"     ["%"];
    V9  : "Cool2PumpCom."        ;
    V10 : "Cool2DXCom."          ;
    V11 : "Heat2Ssignal"    ["%"];
    V12 : "Heat2PumpCom."        ;
    V13 : "El.Heat2Signal"  ["%"];
    V14 : "El.Heat2Com."         ;
   %V15 : ""
    V16 : "HumiditySignal"  ["%"];
    V17 : "HumidityCom."         ;
    V18 : "HumidityPumpCom"      ;
    V19 : "DehumidityValue" ["%"];
   %V20 : ""                     ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg. 37-56" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(36);     % Start address register (37-1)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(V1 := DATA;);
      DATA[5]  -> RWORD(V2 := DATA;);
      DATA[7]  -> RWORD(V3 := DATA;);
      DATA[9]  -> RWORD(V4 := DATA;);
      DATA[11] -> RWORD(V5 := DATA;);
      DATA[13] -> RWORD(V6 := DATA;);
      DATA[15] -> RWORD(V7 := DATA;);
      DATA[17] -> RWORD(V8 := DATA;);
      DATA[19] -> RWORD(V9 := DATA;);
      DATA[21] -> RWORD(V10:= DATA;);
      DATA[23] -> RWORD(V11:= DATA;);
      DATA[25] -> RWORD(V12:= DATA;);
      DATA[27] -> RWORD(V13:= DATA;);
      DATA[29] -> RWORD(V14:= DATA;);
     %DATA[31] -> RWORD(V15:= DATA;);
      DATA[33] -> RWORD(V16:= DATA;);
      DATA[35] -> RWORD(V17:= DATA;);
      DATA[37] -> RWORD(V18:= DATA;);
      DATA[39] -> RWORD(V19:= DATA;);
     %DATA[41] -> RWORD(V20:= DATA;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA3 NAMED "Climatrix Reg.3" TYPEID 21389 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "AuxOperatMode"        ;
    V2  : "AuxTimeSwProg"        ;
    V3  : "AuxAnalogFan"    ["%"];
    V4  : "AlarmOutput1"         ;
    V5  : "AlarmOutput2"         ;
   %V6  : ""
   %V7  : ""
    V8  : "ActAirQualiComp" ["%"];
    V9  : "ActFanCoolValue" ["%"];
    V10 : "ActFanHeatValue" ["%"];
    V11 : "ActFanCompTemp"  ["%"];
    V12 : "ActFanCompHumid" ["%"];
    V13 : "SummerCompFan"   ["%"];
    V14 : "WinterCompFan"   ["%"];
    V15 : "OutAirTemp"     ["°C"];
    V16 : "SupplyAirTemp"  ["°C"];
    V17 : "HeatFrostTemp"  ["°C"];
    V18 : "Act.RoomTemp"   ["°C"];
    V19 : "ExhaustAirTemp" ["°C"];
   %V20 : ""                     ;

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg. 57-76" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(56);     % Start address register (57-1)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(V1 := DATA;);
      DATA[5]  -> RWORD(V2 := DATA;);
      DATA[7]  -> RWORD(V3 := DATA;);
      DATA[9]  -> RWORD(V4 := DATA;);
      DATA[11] -> RWORD(V5 := DATA;);
     %DATA[13] -> RWORD(V6 := DATA;);
     %DATA[15] -> RWORD(V7 := DATA;);
      DATA[17] -> RWORD(V8 := DATA;);
      DATA[19] -> RWORD(V9 := DATA;);
      DATA[21] -> RWORD(V10:= DATA;);
      DATA[23] -> RWORD(V11:= DATA;);
      DATA[25] -> RWORD(V12:= DATA;);
      DATA[27] -> RWORD(V13:= DATA;);
      DATA[29] -> RWORD(V14:= DATA;);

      DATA[31] -> RWORD(IF (DATA>=32768) THEN V15:=(DATA-65536)/10; ELSE V15:=DATA/10; ENDIF;);
      DATA[33] -> RWORD(IF (DATA>=32768) THEN V16:=(DATA-65536)/10; ELSE V16:=DATA/10; ENDIF;);
      DATA[35] -> RWORD(IF (DATA>=32768) THEN V17:=(DATA-65536)/10; ELSE V17:=DATA/10; ENDIF;);
      DATA[37] -> RWORD(IF (DATA>=32768) THEN V18:=(DATA-65536)/10; ELSE V18:=DATA/10; ENDIF;);
      DATA[39] -> RWORD(IF (DATA>=32768) THEN V19:=(DATA-65536)/10; ELSE V19:=DATA/10; ENDIF;);

     %DATA[41] -> RWORD(V20:= DATA;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA4 NAMED "Climatrix Reg.4" TYPEID 21390 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "ExtractAirTemp"  ["°C"]   ;
    V2  : "HeatRSupplyTemp" ["°C"]   ;
    V3  : "HeatRWaterTemp"  ["°C"]   ;
    V4  : "SupplyAirTemp2"  ["°C"]   ;
    V5  : "Heat2FrostTemp"  ["°C"]   ;
    V6  : "AuxiliaryTemp"   ["°C"]   ;
   %V7  : ""                         ;
    V8  : "OutAirHumRelat"  ["%rH"]  ;
    V9  : "OutAirHumAbsol"  ["g/kg"] ;
    V10 : "OutAirEnthalpy"  ["kJ/kg"];
    V11 : "SuppAirHumRel"   ["%rH"]  ;
    V12 : "SuppAirHumAbs"   ["g/kg"] ;
    V13 : "SuppAirEnthal"   ["kJ/kg"];
    V14 : "RoomHumidityRel" ["%rH"]  ;
    V15 : "RoomHumidityAbs" ["g/kg"] ;
    V16 : "RoomEnthalpy"    ["kJ/kg"];
    V17 : "DewPoint"        ["°C"]   ;
   %V18 : ""                         ;
    V19 : "SupplyAirFlow"   ["l/s"]  ;
    V20 : "ExhaustAirFlow"  ["l/s"]  ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg.77-96" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(76);     % Start address register (77-1)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(IF (DATA>=32768) THEN V1 :=(DATA-65536)/10; ELSE V1 :=DATA/10; ENDIF;);
      DATA[5]  -> RWORD(IF (DATA>=32768) THEN V2 :=(DATA-65536)/10; ELSE V2 :=DATA/10; ENDIF;);
      DATA[7]  -> RWORD(IF (DATA>=32768) THEN V3 :=(DATA-65536)/10; ELSE V3 :=DATA/10; ENDIF;);
      DATA[9]  -> RWORD(IF (DATA>=32768) THEN V4 :=(DATA-65536)/10; ELSE V4 :=DATA/10; ENDIF;);
      DATA[11] -> RWORD(IF (DATA>=32768) THEN V5 :=(DATA-65536)/10; ELSE V5 :=DATA/10; ENDIF;);
      DATA[13] -> RWORD(IF (DATA>=32768) THEN V6 :=(DATA-65536)/10; ELSE V6 :=DATA/10; ENDIF;);
     %DATA[15] -> RWORD(V7 := DATA;);
      DATA[17] -> RWORD(V8 := DATA;);
      DATA[19] -> RWORD(IF (DATA>=32768) THEN V9 :=(DATA-65536)/10; ELSE V9 :=DATA/10; ENDIF;);
      DATA[21] -> RWORD(IF (DATA>=32768) THEN V10:=(DATA-65536)/10; ELSE V10:=DATA/10; ENDIF;);
      DATA[23] -> RWORD(V11:= DATA;);
      DATA[25] -> RWORD(IF (DATA>=32768) THEN V12:=(DATA-65536)/10; ELSE V12:=DATA/10; ENDIF;);
      DATA[27] -> RWORD(IF (DATA>=32768) THEN V13:=(DATA-65536)/10; ELSE V13:=DATA/10; ENDIF;);
      DATA[29] -> RWORD(V14:= DATA;);
      DATA[31] -> RWORD(IF (DATA>=32768) THEN V15:=(DATA-65536)/10; ELSE V15:=DATA/10; ENDIF;);
      DATA[33] -> RWORD(IF (DATA>=32768) THEN V16:=(DATA-65536)/10; ELSE V16:=DATA/10; ENDIF;);
      DATA[35] -> RWORD(IF (DATA>=32768) THEN V17:=(DATA-65536)/10; ELSE V17:=DATA/10; ENDIF;);
     %DATA[37] -> RWORD(V18:= DATA;);
      DATA[39] -> RWORD(V19:= DATA;);
      DATA[41] -> RWORD(V20:= DATA;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA5 NAMED "Climatrix Reg.5" TYPEID 21391 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "SupAirPressure"  ["Pa"] ;
    V2  : "ExhAirPressure"  ["Pa"] ;
    V3  : "HeatRFrostPress" ["Pa"] ;
   %V4  : ""                       ;
    V5  : "AirQuality"      ["ppm"];
    V6  : "ExternSetpoint"  ["°C"] ;
   %V7  : ""                       ;
    V8  : "MainHeatSetP"    ["°C"] ;
    V9  : "MainCoolSetP"    ["°C"] ;
    V10 : "SuppHeatSetP"    ["°C"] ;
    V11 : "SuppCoolSetP"    ["°C"] ;
    V12 : "MainHumidiSetP"  ["%rH"];
    V13 : "MainDehumidSetP" ["%rH"];
    V14 : "SuppHumidiSetP"  ["%rH"];
    V15 : "SuppDehumidSetP" ["%rH"];
    V16 : "SuppFanSetP"     ["%"]  ;
    V17 : "ExhaustFanSetP"  ["%"]  ;
   %V18 : "                        ;
    V19 : "SummerCompTemp"  ["°C"] ;
    V20 : "WinterCompTemp"  ["°C"] ;


  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg.97-116" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(96);     % Start address register (97-1)
      DATA[4]  := RWORD(20);     % Number of registers

    ANSWER SIZE 45               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(40);      % Byte count
      DATA[3]  -> RWORD(V1 := DATA;);
      DATA[5]  -> RWORD(V2 := DATA;);
      DATA[7]  -> RWORD(V3 := DATA;);
     %DATA[9]  -> RWORD(V4 := DATA;);
      DATA[11] -> RWORD(V5 := DATA;);
      DATA[13] -> RWORD(IF (DATA>=32768) THEN V6 :=(DATA-65536)/10; ELSE V6 :=DATA/10; ENDIF;);
     %DATA[15] -> RWORD(V7 := DATA;);
      DATA[17] -> RWORD(IF (DATA>=32768) THEN V8 :=(DATA-65536)/10; ELSE V8 :=DATA/10; ENDIF;);
      DATA[19] -> RWORD(IF (DATA>=32768) THEN V9 :=(DATA-65536)/10; ELSE V9 :=DATA/10; ENDIF;);
      DATA[21] -> RWORD(IF (DATA>=32768) THEN V10:=(DATA-65536)/10; ELSE V10:=DATA/10; ENDIF;);
      DATA[23] -> RWORD(IF (DATA>=32768) THEN V11:=(DATA-65536)/10; ELSE V11:=DATA/10; ENDIF;);
      DATA[25] -> RWORD(IF (DATA>=32768) THEN V12:=(DATA-65536)/10; ELSE V12:=DATA/10; ENDIF;);
      DATA[27] -> RWORD(IF (DATA>=32768) THEN V13:=(DATA-65536)/10; ELSE V13:=DATA/10; ENDIF;);
      DATA[29] -> RWORD(IF (DATA>=32768) THEN V14:=(DATA-65536)/10; ELSE V14:=DATA/10; ENDIF;);
      DATA[31] -> RWORD(IF (DATA>=32768) THEN V15:=(DATA-65536)/10; ELSE V15:=DATA/10; ENDIF;);
      DATA[33] -> RWORD(V16:= DATA;);
      DATA[35] -> RWORD(V17:= DATA;);
     %DATA[37] -> RWORD(V18:= DATA;);
      DATA[39] -> RWORD(IF (DATA>=32768) THEN V19:=(DATA-65536)/10; ELSE V19:=DATA/10; ENDIF;);
      DATA[41] -> RWORD(IF (DATA>=32768) THEN V20:=(DATA-65536)/10; ELSE V20:=DATA/10; ENDIF;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA6 NAMED "Climatrix Reg.6" TYPEID 21392 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "HeatRec.PumpCom"      ;
    V2  : "HeatDamperSigna" ["%"];
   %V3  : ""                     ;
    V4  : "HeatDamperValue" ["%"];
    V5  : "HeatSignal"      ["%"];
    V6  : "HeatPumpCom."         ;
    V7  : "El.HeatSignal"   ["%"];
    V8  : "El.HeatCom."          ;

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg 117-124" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(116);    % Start address register (117-1)
      DATA[4]  := RWORD(8);      % Number of registers

    ANSWER SIZE 21               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(16);      % Byte count
      DATA[3]  -> RWORD(V1 := DATA;);
      DATA[5]  -> RWORD(V2 := DATA;);
     %DATA[7]  -> RWORD(V3 := DATA;);
      DATA[9]  -> RWORD(V4 :=DATA/10;);
      DATA[11] -> RWORD(V5 :=DATA/10;);
      DATA[13] -> RWORD(V6 :=DATA/10;);
      DATA[15] -> RWORD(V7 :=DATA/10;);
      DATA[17] -> RWORD(V8 :=DATA/10;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog inputs
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Note! Telegram for reading Analog status AI and AO
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixA7 NAMED "Climatrix Reg.7" TYPEID 21393 IS

  PARAMETER
    Id         : "Adress";

  PUBLIC

    V1  : "HeatRec.PumpCom"         ;
    V2  : "HeatDamperSigna" ["K/°C"];
    V3  : "HeatDamperValue" ["°C"]  ;
    V4  : "HeatSignal"      ["°C"]  ;

  PRIVATE

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM AnalogInput NAMED "Läs reg.200-203" IS
    QUESTION
      DATA[0]  := BYTE(Id);      % Modbus unit address
      DATA[1]  := HEX(04);       % Modbus command "04h" Read registers
      DATA[2]  := RWORD(199);    % Start address register (200-1)
      DATA[4]  := RWORD(4);      % Number of registers

    ANSWER SIZE 13               % (Number of registers * 2) + 5
      DATA[0]   = BYTE(Id);      % ID
      DATA[1]   = HEX(04);       % Modbus command "04h" Read registers
     %DATA[2]   = BYTE(8);       % Byte count
      DATA[3]  -> RWORD(V1 := DATA;);
      DATA[5]  -> RWORD(IF (DATA>=32768) THEN V2:=(DATA-65536)/10; ELSE V2:=DATA/10; ENDIF;);
      DATA[7]  -> RWORD(IF (DATA>=32768) THEN V3:=(DATA-65536)/10; ELSE V3:=DATA/10; ENDIF;);
      DATA[9]  -> RWORD(IF (DATA>=32768) THEN V4:=(DATA-65536)/10; ELSE V4:=DATA/10; ENDIF;);

    TIMEOUT 1000

  END;

END;

%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%%
% Device definition for Climatrix Analog settings
%
% Settings module:
%       Parity:	None
%       Baud:   9600
%       Mode:   RTU
%
% Author:  Peter Widetun, ABELKO AB Luleå
% History: 2010-08-18 inital version
%
DEVICETYPE ClimatrixSet NAMED "Climatrix Ställ" TYPEID 21294 IS

  PARAMETER
    Id  : "Adress";

   S20  : "ComfortTempSetP" ["°C"] ;  % 4x0020 Comfort temperature setpoint -+ °C (factor 10)

  PUBLIC

  PRIVATE
    Cnt;

  BAUDRATE 9600;

  CHECKSUM MODBUS SWAPPED;

  TELEGRAM Settings1 NAMED "Ställ värden" IS

    QUESTION
      DATA[0]  := BYTE(Id);
      DATA[1]  := HEX(06);                %Write singel register
      DATA[2]  <- RWORD(                  %Start adress (regnr-1)
        IF Cnt>8 THEN Cnt:=0; ENDIF;
        %%                Adress=Register-1
        IF    Cnt=0 THEN DATA := 19;     % S20
        ELSIF Cnt=1 THEN DATA := 19;     % S20
        ELSIF Cnt=2 THEN DATA := 19;     % S20
        ELSIF Cnt=3 THEN DATA := 19;     % S20
        ELSIF Cnt=4 THEN DATA := 19;     % S20
        ELSIF Cnt=5 THEN DATA := 19;     % S20
        ELSIF Cnt=6 THEN DATA := 19;     % S20
        ELSIF Cnt=7 THEN DATA := 19;     % S20
        ELSE             DATA := 19;     % S20
        ENDIF;
      );

      DATA[4]  <- RWORD(

        IF    Cnt=0 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=1 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=2 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=3 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=4 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=5 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=6 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSIF Cnt=7 THEN
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ELSE
          IF    S20<10    THEN DATA := 100;   % S20 Comfort temperature setpoint 1/10
          ELSIF S20>30    THEN DATA := 300;
          ELSE                 DATA := S20;
          ENDIF;
        ENDIF;

        Cnt := Cnt + 1;
        IF Cnt>8 THEN Cnt := 0;
        ENDIF;
      );

    ANSWER SIZE 8
      DATA[0] = BYTE(Id);
      DATA[1] = HEX(06);

    TIMEOUT 1000

  END;

END;