% Skapad med Modbus Creator % - OBS! Användaren ansvarar själv för att samma TYPID inte används flera gånger i samma apparat. % TYPID 10000-19999 är för användardefinierade enheter DEVICETYPE IV_AHUClimatix NAMED "IV_AHUClimatix" TYPEID 10718 IS PARAMETER Id : "Adress"; PUBLIC V1 : "Manual mode" [""]; V2 : "OperatingMode" [""]; % 0=off, 1=on/comfort, 5=nightcooling, 6=unoccupied(tem start), 12=startup V3 : "ActFanStep" [""]; % 0=off, stage 1-3 V4 : "ManOpSteps" [""]; % 0=auto, 1=off, 2-4= step 1-3 V5 : "OutsideAirDamper" [""]; % 0=off V6 : "ExtractAirDamper" [""]; % 0=off V7 : "SupplyFanOut" ["%"]; V8 : "ExhaustFanOut" ["%"]; V9 : "CoolingOut" ["%"]; V10 : "CoolingPumpCmd" ["%"]; % on/off V11 : "HeatRecOut" ["%"]; V12 : "HeatingOut" ["%"]; V13 : "HeatingPumpCmd" [""]; % off/on V14 : "OutsideTemp" ["°C"]DEC1; V15 : "SupplyTemp" ["°C"]DEC1; V16 : "HeatingFrostTemp" ["°C"]DEC1; V17 : "ExhaustTemp" ["°C"]DEC1; V18 : "HeatingSP" ["°C"]DEC1; V19 : "SupplyHeatSP" ["°C"]DEC1; V20 : "SupplyCoolingSP" ["°C"]DEC1; PRIVATE BAUDRATE 9600; CHECKSUM MODBUS SWAPPED; TELEGRAM Read1 NAMED "Read 1" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(01); % Modbus kommando för att läsa register kod 01 DATA[2] := RWORD(4); % Start address DATA[4] := RWORD(1); % Antal register att läsa ANSWER SIZE 6 % (Antal register / 8) avrundat uppåt + 5 DATA[0] = BYTE(Id); DATA[1] = BYTE(01); DATA[2] = BYTE(1); % Antal Bytes DATA[3] -> BYTE( IF (DATA & 1) THEN V1 := 1; ELSE V1 := 0; ENDIF; ); TIMEOUT 300 END; TELEGRAM Read4 NAMED "Read 4" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(04); % Modbus kommando för att läsa register kod 04 DATA[2] := RWORD(16); % Start address DATA[4] := RWORD(91); % Antal register att läsa ANSWER SIZE 187 % (Antal register * 2) + 5 DATA[0] = BYTE(Id); DATA[1] = BYTE(04); DATA[2] = BYTE(182); % Antal Bytes DATA[3] -> RWORD(V2 := DATA;); DATA[5] -> RWORD(V3 := DATA;); DATA[7] -> RWORD(V4 := DATA;); DATA[19] -> RWORD(V5 := DATA;); DATA[21] -> RWORD(V6 := DATA;); DATA[27] -> RWORD(V7 := DATA;); DATA[31] -> RWORD(V8 := DATA;); DATA[35] -> RWORD(V9 := DATA;); DATA[37] -> RWORD(V10 := DATA;); DATA[41] -> RWORD(V11 := DATA;); DATA[49] -> RWORD(V12 := DATA;); DATA[51] -> RWORD(V13 := DATA;); DATA[113] -> RWORD(V14 := DATA/10;); DATA[115] -> RWORD(V15 := DATA/10;); DATA[117] -> RWORD(V16 := DATA/10;); DATA[121] -> RWORD(V17 := DATA/10;); DATA[177] -> RWORD(V18 := DATA/10;); DATA[181] -> RWORD(V19 := DATA/10;); DATA[183] -> RWORD(V20 := DATA/10;); TIMEOUT 300 END; END; % Skapad med Modbus Creator % - OBS! Användaren ansvarar själv för att samma TYPID inte används flera gånger i samma apparat. % TYPID 10000-19999 är för användardefinierade enheter DEVICETYPE IV_AHUClimatix2 NAMED "IV_AHUClimatix2" TYPEID 10719 IS PARAMETER Id : "Adress"; PUBLIC V1 : "ONC(Steps)" [""]; % auto*off*stage1-3 V2 : "ComfortTempDZ" ["°C"]DEC1; V3 : "ComfortHeatSP" ["°C"]DEC1; V4 : "SummerWinterComp" ["°C"]DEC1; V5 : "SupplyTempMinSP" ["°C"]DEC1; V6 : "SupplyTempMaxSP" ["°C"]DEC1; V7 : "SupplyFanSt1SP" [""]; % %, Pa, l/s V8 : "SupplyFanSt2SP" [""]; V9 : "SupplyFanSt3SP" [""]; V10 : "ExhaustFanSt1SP" [""]; V11 : "ExhaustFanSt2SP" [""]; V12 : "ExhaustFanSt3SP" [""]; V13 : "TempStartHeatStart" ["°C"]DEC1; V14 : "TemStartHeatSP" ["°C"]DEC1; V15 : "SupplyFanSP" [""]; % %, Pa, l/s V16 : "ExhaustFanSP" [""]; % %, Pa, l/s PRIVATE BAUDRATE 9600; CHECKSUM MODBUS SWAPPED; TELEGRAM Read3 NAMED "Read 3" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(03); % Modbus kommando för att läsa register kod 03 DATA[2] := RWORD(4); % Start address DATA[4] := RWORD(71); % Antal register att läsa ANSWER SIZE 147 % (Antal register * 2) + 5 DATA[0] = BYTE(Id); DATA[1] = BYTE(03); DATA[2] = BYTE(142); % Antal Bytes DATA[3] -> RWORD(V1 := DATA;); DATA[35] -> RWORD(V2 := DATA/10;); DATA[37] -> RWORD(V3 := DATA/10;); DATA[57] -> RWORD(V4 := DATA/10;); DATA[65] -> RWORD(V5 := DATA/10;); DATA[67] -> RWORD(V6 := DATA/10;); DATA[93] -> RWORD(V7 := DATA;); DATA[95] -> RWORD(V8 := DATA;); DATA[97] -> RWORD(V9 := DATA;); DATA[101] -> RWORD(V10 := DATA;); DATA[103] -> RWORD(V11 := DATA;); DATA[105] -> RWORD(V12 := DATA;); DATA[141] -> RWORD(V13 := DATA/10;); DATA[143] -> RWORD(V14 := DATA/10;); TIMEOUT 300 END; TELEGRAM Read4 NAMED "Read 4" IS QUESTION DATA[0] := BYTE(Id); % Enhetens Modbus adress DATA[1] := HEX(04); % Modbus kommando för att läsa register kod 04 DATA[2] := RWORD(111); % Start address DATA[4] := RWORD(2); % Antal register att läsa ANSWER SIZE 9 % (Antal register * 2) + 5 DATA[0] = BYTE(Id); DATA[1] = BYTE(04); DATA[2] = BYTE(4); % Antal Bytes DATA[3] -> RWORD(V15 := DATA;); DATA[5] -> RWORD(V16 := DATA;); TIMEOUT 300 END; END;